Overview
HRP-T1000-CL2 Chlorine Gas Detector is an explosion-proof Gas detection equipment of HUIRUIPU brand. It adopts Catalytic combustion Sensor and Electrochemical sensor technology imported from the United States, which has the advantages of stable signal and high accuracy. The instrument shell adopts cast aluminum one-time molding explosion-proof and explosion-proof design, which is suitable for flammable, explosive and toxic and harmful gas leakage detection in various dangerous places.
Features
1. Adjustable detection accuracy and range
2. Long Life, High Sensitivity, Low drift, Stable and Reliable
3. Two-stage concentration alarm with relay output function
4. LCD display and working status display
5. With temperature compensation, automatic zero correction function
6.4~ 20mA standard Analog Output and RS485 digital output, can be uploaded to DCS, PLC system
7. Infrared remote control method, the detector can be adjusted without opening the lid, which is safe and convenient
8. Flameproof design suitable for hazardous conditions 1 and 2 zones
Principle
The system provides 24V standard DC voltage to the external transmitter, collects the input signal of the standard 4-20mA transmitter, and analyzes and processes it to complete the digital display and alarm operation.
Applications
Petroleum exploration and production, oil and gas transportation, oil refining, metallurgy, power plants, chemical industry, oil depots, liquefied gas stations, mines, tunnels, tunnels, underground pipelines
Standards
Explosion-proof marking: Ex d ⅱ C T6 Gb
Steps
1. Use the infrared remote control for debugging
2. Connect the power supply and signal output line
3. Monitor LCD display and status indicator
Notice
• Working ambient temperature range -20~ + 50 ℃
The working environment humidity should be less than 95%
• Use cable specifications ≥ 1.5mm ² × 3 or ≥ 1.5mm ² × 4
• The maximum distance between the detector and the host does not exceed 1000m
• Operating Pressure Range: 86~ 106kPa