Catalytic combustion Sensor, Range 0-100% LEL, Resolution 0.1% LEL, Response Time ≤ 30 seconds. With automatic temperature compensation, anti-concentration Impact Protection and Full Software Adjustment, support 4-20mA and RS485 output, flameproof structure is suitable for hazardous environments.
Category : Gas Detector
Brand : Skyeaglee
SKU : NB036975
Service :The delivery and service By NBCLab.Com
SK/MIC-600-CH4-Y Online Methane Detector is a flammable gas monitor with Modular design, intelligent Sensor detection technology, overall flameproof (d) structure, and fixed Installation method. The standard configuration is a dot matrix LCD liquid crystal display, three-wire 4~ 20mA analog and RS485 digital signal output, optional configuration of programmable switch output and other modules, support Output signal fine-tuning and other functions, convenient system networking and maintenance.
1. Modular design, intelligent Sensor detection technology, the overall flameproof (d) structure. 2. Automatic temperature compensation, zero point, full scale drift compensation. 3. Automatic protection against high concentration gas Impact. 4. Full software Adjustment, users can also calibrate themselves through 3 buttons, easy to operate. 5. Standard configuration for point matrix LCD liquid crystal display, three-wire system 4~ 20mA analog and RS485 digital signal output. 6. Optional configuration of programmable switch output and other modules, support Output signal fine-tuning, convenient system networking and maintenance.
The detector adopts the principle of catalytic combustion Sensor. Sampling methods such as diffusion, pipeline, flow or pump suction are used to continuously monitor the concentration of methane gas in the environment. The detected concentration signal is processed and converted into standard current signal output.
Paints room, incinerator, scientific research, production workshop, company, environment monitoring, school scientific research, building construction, fire alarm, sewage treatment, industrial gas process control, petroleum and petrochemical, chemical plant, smelter, steel plant, coal plant, thermal power plant, boiler room, waste treatment plant, tunnel construction, oil pipeline, gas station, underground gas pipeline maintenance, indoor air mass detection, safety protection equipment monitoring in dangerous places, etc.
Explosion-proof mark: ExdIICT6, Protection Rating: IP66
1. Make the correct wiring according to the electrical wiring definition diagram. 2. Connect DC12~ 30V Power Supply. 3. After the instrument is powered on, the reading is observed through the point matrix LCD liquid crystal display. 4. If you need to calibrate, you can enter the calibrate mode through the 3 buttons on the instrument and follow the prompts.
* Working ambient temperature range is -20 ℃~ + 50 ℃, Humidity range is 10% RH~ 90% RH (no condensation). The absolute pressure should be within the range of 106KPa +/- 20KPa. It is recommended to use a three-core Shielding cable with a single wire diameter of ≥ 1.5mm for connection, and the connection distance should be ≤ 1000m. * Sensors have a lifespan of approximately 2 years and require regular maintenance and calibrating. Installation and operation are subject to relevant explosion-proof safety regulations. The specific selection should be determined according to the actual working conditions.
[A] No, it isn't. This is the ex-factory price of the product in the Chinese Mainland. In addition to this price, buyers from different countries need to account for additional costs such as shipping fees, tariffs, and others. For specific regional quotes, please consult our customer service or fill out a quotation form.
[A] First, please click on the quotation form on the website and fill in detailed information. Our customer service personnel will then send you a quotation based on your specific country and region, confirming payment and delivery methods. Following this, we proceed with contract signing, payment, and shipment. You can then await delivery.
[A] After-sales repair for overseas instruments is an unavoidable issue. Our repair terms stipulate that the sender is responsible for the shipping and insurance costs incurred for the repair. Repairs within the warranty period are free, while repair costs beyond the warranty period are determined based on the actual situation.