Overview
SK/MIC-600-NH3-Y/500 online ammonia gas detector is a fixed-mounted gas concentration detector with Modular design, intelligent Sensor detection technology and overall flameproof (d) structure of SKYEAGLEE brand. The instrument standard configuration has dot matrix LCD liquid crystal display, supports three-wire 4~ 20mA analog and RS485 digital signal output, and can provide customized modules such as programmable switch output according to user request, which is convenient for system networking and maintenance.
Features
1. Modular design is adopted to support customization.
2. Sensor detection technology.
3. Integral flameproof (d) structure, suitable for use in hazardous locations.
4. Automatic temperature compensation, zero point and full scale drift compensation.
5. Impacts against high concentration gases with automatic protection function.
6. Support full software calibrate, users can calibrate by themselves through 3 buttons, easy to operate.
7. Provide 2-wire 4-20mA output.
Principle
The detector adopts the Sensor of electrochemistry principle to continuously monitor the ammonia (NH3) concentration in the environment through the Sampling method of diffusion type, pipeline type, flow type or pump type. The detected gas concentration signal is processed and converted into a standard 4-20mA current signal or RS485 digital signal output.
Applications
Paints room, incineration plant, scientific research, production workshop, environment monitoring, school scientific research, building construction, fire alarm, sewage treatment, industrial gas process control, petroleum and petrochemical, chemical plant, smelter, steel plant, coal plant, thermal power plant, boiler room, waste treatment plant, tunnel construction, oil pipeline, gas station, underground gas pipeline maintenance, indoor air mass detection, safety protection equipment monitoring in dangerous places, etc.
Steps
1. Installation: Connect the power supply and signal lines according to the electrical wiring definition diagram.
2. Power on: Connect to DC12~ 30V Operating voltage.
3. Calibrate: Use the 3 buttons on the instrument to enter the calibrate mode to calibrate the zero point and range.
4. Settings: Set parameters such as alarm points through buttons.
5. Operation: The instrument starts to continuously monitor and display the concentration, and output the corresponding signal.
Notice
• Please select according to the actual working conditions, the information is for reference only.
• Working ambient temperature range is -20 ℃~ + 50 ℃, Humidity is 10% RH~ 90% RH without condensation.
• Absolute pressure should be within the range of 106KPa +/- 20KPa.
• It is recommended to use a Shielding cable with a connection distance of no more than 1000 meters.
• Sensors have a lifespan of approximately 2 years and require regular maintenance and calibrating.
• The instrument is flameproof, and the installation and maintenance must comply with relevant explosion-proof safety regulations.