HUIRUIPU HRP-K6000-32 split-line gas alarm controller is a device for detecting flammability gas or toxic gas content in the air. It supports multiple 4-20mA signal inputs and can centrally control multiple points at the same time. The system uses a microprocessor as the Control Unit. When the gas concentration in the environment reaches or exceeds the preset value, it immediately emits sound and light alarms, and drives the exhaust or Miscellaneous peripherals through relays to prevent explosions and fire accidents and ensure life safety.
Features
1. Supports multiple 4-20mA signal inputs, capable of controlling 32 detectors simultaneously
2. Microprocessor Control Unit for Fast Response
3. With sound and light alarm function, including indicator light and buzzer
4. Provide four sets of passive relay outputs to drive external devices
5. Equipped with 7-inch color screen and touch operation interface
6. It can store 20,000 alarm records
7. Support RTU-standard modbus protocol data upload
8. Users can freely set two alarm points
Principle
The controller monitors the concentration of flammability or toxic gases in the environment in real time by receiving a 4-20mA signal from the detector. When the concentration reaches or exceeds the alarm value preset by the user, the microprocessor Control Unit immediately triggers the sound and light alarm, and drives the exhaust system or Miscellaneous external equipment through the relay output to achieve safety protection.
Applications
Factory, oil depot, liquefied gas station, gas station, gas station, spray booth
Steps
1. Use the [OK] key to enter the menu or confirm the function
2. Use the [Up] key to select menu items or perform shift operations
3. Use the [Down] key to select menu items or change values
4. Use the [Exit] key to return to the previous level menu or exit. It can also be used as the [Muffler] function when static.
Notice
• Operating voltage is AC220V +/- 10% 50HZ
• Working ambient temperature range -10~ 50 ℃
• Working environment humidity does not exceed 95% RH
• Maximum system power consumption is 10W (without external devices)
• Wiring needs to use ≥ RVVP2 * 1.5 national standard Shielding wire, single core wire diameter ≥ 1.5mm, wire length does not exceed 1000m
• Backup power supply is 24V 1.3AH lead-acid battery (optional)
• The installation method is on-site fixed wall installation