Support simultaneous detection of 4 gases, integrated temperature and Humidity detection, with Internet of Things remote monitoring function, Response Time T90 ≤ national standard, Protection Rating IP66, suitable for a variety of Installation methods.
Category : Gas Detector
Brand : Empaer
SKU : NB049614
Service :The delivery and service By NBCLab.Com
Pathfinder series stationary methane detector (sound and light alarm) is a high-performance and fully functional mid-to-high-end on-site gas monitoring instrument launched by Empaer brand. It supports the detection of 4 gases at the same time and has its own temperature and Humidity detection. The product can convert the detected gas concentration and temperature and Humidity into standard signals and transmit them to PLC, DCS and other host computers for unified management. The built-in relay can control sound and light alarms, fans and other peripheral devices, and supports remote monitoring and setting of the Internet of Things.
1. Support diffusion and pump-suction Sampling method, maximum simultaneous detection of 4 gas types, integrated temperature and Humidity detection 2. Internet of Things function: remote monitoring, alarm setting and program upgrade can be realized through NB-IoT, 4G or WIFI connection server 3. Independent design of shell molds, high brand recognition 4. High standard and high performance, with reference to a variety of industry standards, the product is stable and reliable 5. Ultra high definition 2.0 inch color display, viewing distance of 10 meters 6. Complete certification: double explosion-proof certification, CPA certification, SIL2 certification, CE certification, CNAS metrology authentication 7. Support multiple Wireless Communication modes (optional) 8. Double Temperature Humidity Design, Physical + Software Double Compensation 9. Bilingual Operating system 10. Installation methods: Wall-Mounted, Rod, Ceiling, Pipeline 11. Black box storage functions: operation records, alarm records, etc 12. Complete reminder and alarm functions 13. Operating interface with guide function to prevent misoperation 14. Zero automatic correction function 15. Waterproof, dustproof, anti-static, anti-electromagnetic interference
The detector detects on-site gas concentration and temperature Humidity through Sensor, converts the detection data into standard signals (such as 4-20mA, RS-485, etc.), and then transmits it to PLC, DCS, alarm control host and other host computers for unified display, management and control. Built-in relays can control peripheral equipment such as sound and light alarms, fans, solenoid valves, etc., to realize intelligent Gas detection and alarm control.
Petroleum and petrochemical, mining, gas, aerospace and military, chemical industry, electric power, scientific research institutes, municipal engineering, metallurgy
Measurement equipment CPA, CCCF, Flameproof, Intrinsic Safety (IS), IP66 protection, Mine safety, Coal safety, ROSH, SIL2, CE, ATEX, IEC
1. Select the appropriate Installation method (Wall-Mounted, Rod, Ceiling or Pipeline) for installation 2. Connect the power supply (12~ 36VDC, typical 24VDC) 3. Connect wired signal output (such as 4-20mA, RS-485, etc.) or wireless signal output as needed 4. Parameter configuration through infrared remote control or remote IoT 5. Set the alarm value and related parameters 6. Perform automatic zero correction 7. Start the detection system to monitor gas concentration and Humidity data
The recommended calibration period is one year • Working ambient temperature range is -40~ 55 ℃, storage temperature is -10~ 30 ℃ • Environmental humidity range of 10% -95% RH (no condensation) • Operating Pressure Range 86-106KPA • Protection Rating IP66, Explosion-proof level Exd II C T6, EX TD A21 • Power consumption is less than 2W, depending on the Sensor • Support watch head and Probe split, the maximum distance is 100 meters • Self-upgrading software through remote IoT OTA upgrade or local installation package • Sensor automatic protection function (optional)
[A] No, it isn't. This is the ex-factory price of the product in the Chinese Mainland. In addition to this price, buyers from different countries need to account for additional costs such as shipping fees, tariffs, and others. For specific regional quotes, please consult our customer service or fill out a quotation form.
[A] First, please click on the quotation form on the website and fill in detailed information. Our customer service personnel will then send you a quotation based on your specific country and region, confirming payment and delivery methods. Following this, we proceed with contract signing, payment, and shipment. You can then await delivery.
[A] After-sales repair for overseas instruments is an unavoidable issue. Our repair terms stipulate that the sender is responsible for the shipping and insurance costs incurred for the repair. Repairs within the warranty period are free, while repair costs beyond the warranty period are determined based on the actual situation.